The dedicated section gives designers clear requirements for using thermal imaging inside the fire alarm system. Listing and approval routes include UL 2684 and FM 3260, supporting earlier detection of developing heat.
This guide explains what changed, what did not, and what it means from two points of view: the insurer pricing the risk and the manufacturer running the plant. We also explain where AVIAN fits.
1. A new definition (3.3.79.26). A thermal image fire detector is "an initiating device that senses overheated combustible material by imaging in the long-wave infrared wavelengths (i.e., far infrared) using a focal plane array." In plain English: a thermal camera that can start a fire alarm signal. The definition of "detector" itself was also broadened to include sensors that respond to light and sound, to make room for new detection methods.
2. A new section on design and installation (17.12). The technical committee explained why it was needed. Thermal imagers are technically radiant energy detectors, but the existing radiant energy rules were written for traditional non-imaging flame and spark detectors. New products look for overheated areas across a whole field of view, so they needed their own rules.
Section 17.12 is short. Most of its weight comes from a few requirements. The table below summarizes them based on the committee's first revision text and published summaries from Consulting-Specifying Engineer. Check the published edition for exact wording.
Requirement
What it means in practice
Listed for fire detection, including hardware and software
Specify a system listed for fire detection, covering its hardware, software, and intended application.
Performance-based design (Section 17.3)
There is no simple spacing table. An engineer designs coverage around the hazard and documents the objectives.
Clear line of sight to the protected hazard
The detector must see the thing that can burn. Obstructions, racking, and enclosures matter.
No pan-tilt mounts unless listed for movement
Detection is expected from a fixed view, not a camera that sweeps away from the hazard.
Outputs to other systems only through manufacturer-provided connections
Signals can feed PLCs or other systems, but only through outputs designed for that purpose.
Controls and software protected from unauthorized changes
Alarm settings cannot be casually edited. Configuration must be locked down.
Any software or setting change retested under Chapter 14
Changing a zone or threshold is a fire alarm change. It needs testing and records.
Supervisory signal if the lens is blocked or dirty
The system must tell you when it can no longer see. This matters in dusty plants.
Able to alarm on temperature rate of rise in the field of view
The detector must catch fast-developing heat, not only a fixed temperature threshold.
Two things stand out.
First, the code treats a thermal fire detector as a system, not just a camera. Software, settings, outputs, and supervision are all in scope.
Second, the code assumes the view can degrade. Dirt, dust, and blocked lenses are named failure modes. Anyone who has run a camera in a sawmill or recycling plant knows why.
UL 2684 and FM 3260: Listing and Approval Routes
Section 17.12.1 requires listing for fire detection. It does not name UL as the sole listing organization or require UL 2684 as the only route. UL 2684 listing and FM 3260 approval provide paths for thermal fire detection and fire alarm panel integration.
UL 2684, Video and Thermal Image Detectors for Fire Alarm Systems, covers imaging detectors used as part of fire alarm systems under NFPA 72. Its scope includes detecting heat at infrared wavelengths with a focal plane array, for indoor use and, for thermal detectors, outdoor use. Its current edition was ANSI approved in August 2025.
On September 22, 2026, Teledyne FLIR announced that its A40, A50, and A70 cameras were the first thermal imagers listed to UL 2684.
For either route, match the listed or approved configuration to the hazard, panel interface, and installation requirements. The fire alarm designer and AHJ confirm the application as part of the system design.
What Did Not Change
The new section fits into the facility's existing fire protection design:
Nothing requires you to install thermal cameras. The 2025 edition sets rules for thermal image fire detectors when they are used. It does not mandate them.
Your jurisdiction decides which edition applies. States and cities adopt NFPA 72 on their own schedule. Many sites still operate under older editions.
Sprinklers, smoke detection, and suppression stay. A thermal detector covers only what it can see. It does not replace code-required protection elsewhere.
Specify the listing for the application. UL 2684 listing and FM 3260 approval are routes to consider alongside the system design and panel interface.
The code keeps moving. The committee is working on the 2028 edition now. Expect refinements as field experience grows.
For Insurers
For underwriters, brokers, and risk engineers, the change gives thermal monitoring a vocabulary it did not have before.
Until now, a facility that said "we have thermal cameras" could mean almost anything. A handheld used once a quarter. A fixed camera that emails a supervisor. A fully engineered detection system tied to shutdowns. The underwriting file rarely made the difference clear.
NFPA 72, together with listing and approval routes such as UL 2684 and FM 3260, gives thermal systems clear roles in the protection plan.
Three roles thermal cameras can play
Listed fire detection. A thermal image fire detector, listed to UL 2684 or approved to FM 3260, designed under Section 17.12 and connected to the fire alarm system. It carries code standing, supervision, and a Chapter 14 testing record.
Supplemental early warning and condition monitoring. A fixed thermal monitoring system that watches equipment and material, alerts operations and maintenance, and often triggers PLC actions. Its focus is prevention: catching the hot bearing, loose connection, or smoldering load before it becomes a fire.
Both. Listed detection where code or policy requires it, plus supplemental monitoring on the assets most likely to start the fire.
Each role deserves credit for different reasons. Listed detection reduces the severity of a fire that has started by alarming earlier. Supplemental monitoring reduces frequency by stopping ignition sources. Many industrial losses begin as heat long before smoke. That prevention work gives the risk engineer measurable evidence of how the facility catches and resolves developing hazards.
What to ask during a risk review
Is the thermal system part of the fire alarm system, or a supplemental layer?
If listed, to which standard: UL 2684, FM 3260, or something else?
Who designed the coverage, and is there a written performance-based design?
Which hazards are in direct line of sight, and which are not?
How does the system report a blocked, dirty, or offline camera?
Who can change alarm settings, and is every change logged and tested?
Where do alarms go, and how fast does someone respond?
Can the site show real event history and corrective actions from the last 12 months?
Evidence of effective protection
A coverage map shows which surfaces and hazards the cameras can see. Event records show how quickly teams investigate alerts and close corrective actions. For a fire alarm application, the listing or approval documents and manufacturer's test records complete the picture.
Together, those records show how the system performs in daily operation and how the facility responds to developing heat.
If you run a sawmill, recycling plant, pellet mill, food plant, or any heavy industrial site, the first question is simple: does this force me to do anything?
Usually not. The code does not require thermal detection. But it changes three conversations you are likely to have soon.
1. Your insurer and AHJ now have a reference point
Expect more specific questions at renewal and during plan review. "What role does your thermal system play?" is now a fair question with a defined answer. Have one ready.
2. You need to decide what job the camera is doing
Before buying anything, decide which of these you need:
Code-required or insurer-required fire detection for a specific hazard. That points to a listed thermal image fire detector, a fire protection engineer, and your fire alarm contractor.
Fire prevention and uptime on conveyors, motors, bearings, panels, dust systems, and material piles. That points to a thermal monitoring system that learns normal behavior, alerts your team, and integrates with your controls.
Both, which is common in high-risk plants.
These functions can work together. Fire alarm initiation provides a defined emergency response, while continuous temperature trends help maintenance find and correct the underlying equipment problem. Choose the system and integration around both objectives.
3. Plan for reliable operation
If you install listed thermal image fire detectors, plan for what Section 17.12 implies:
Engineering. Performance-based design means someone has to document objectives, hazards, and coverage.
Fixed, clean views. Plan mounts, guards, and lens cleaning. In dusty areas, the supervisory signal for a dirty lens will tell you how often.
Change control. Adjusting a zone is now a fire alarm change. Budget time for retesting and records.
Ownership. Your fire alarm contractor, controls team, and maintenance team all touch this system. Decide who owns what.
Clear responsibilities and a practical maintenance schedule keep detection reliable.
Where thermal prevention still pays off
Most plant fires do not start in open space. They start at equipment: a dragging roller, an overloaded motor, a hot electrical connection, a dust duct carrying embers. The same heat that signals fire risk also signals a coming failure.
That is why many manufacturers get more value from continuous thermal monitoring on critical assets than from detection alone. It prevents fires and downtime from the same data. See what condition-based monitoring with thermal imaging looks like in practice.
What This Means for AVIAN Customers
We have been saying for years that heat is the first warning. NFPA 72 now agrees that heat seen through a thermal imager is a legitimate fire signal. That is good for the whole category.
AVIAN turns developing heat into action. The AVIAN T100 continuously monitors equipment and material, learns normal temperature behavior, and gives teams the thermal and visible context to respond early. Operations can investigate a hot load, maintenance can correct a failing bearing, and plant controls can act on an alarm before the problem escalates.
The engineering principles in 17.12 are already how we deploy. The code's requirements describe what a reliable thermal system needs. AVIAN was built around the same ideas for prevention.
NFPA 72 17.12 principle
How AVIAN approaches it
Clear line of sight to the hazard
Coverage is planned asset by asset, with fixed T100 mounts aimed at the conveyors, motors, panels, and piles that matter.
Know when the view is lost
Tamper detection alerts when a camera is blocked, misaligned, or offline.
Catch developing heat, not just a fixed limit
The T100 learns each asset's normal temperature and flags drift as it starts, filtered by visual context to cut nuisance alarms.
Access is controlled under our SOC 2 Type II program, and every alert, acknowledgement, and response time is logged.
An AVIAN deployment brings coverage planning, camera-status monitoring, controlled settings, and response records into the same workflow. That gives plant teams useful operating evidence and insurers a clearer picture of how developing hazards are handled.
Connect detection with a practical response. Build the protection plan around:
Fire detection and alarm integration matched to the hazard and applicable listing or approval.
AVIAN on the equipment and material most likely to start a fire, where abnormal heat appears hours or days before an alarm-worthy event.
One response workflow that routes heat alerts to the people and PLCs that can act.
For insurers, that plan is easy to document. For plant teams, it means one system pays for itself through avoided downtime while also lowering fire risk.
The Bottom Line
NFPA 72 2025 did not make thermal cameras mandatory. It made them legitimate fire alarm devices, with rules to match: listing, engineered design, line of sight, supervision, locked configuration, and documented testing.
For insurers, the useful question is now specific: what role does this thermal system play, and what evidence backs it?
For manufacturers, the useful question is: what job do we need the camera to do? Code detection, prevention and uptime, or both?
Answer those two questions honestly and the rest of the decision gets easier.
If you want help mapping which areas of your facility need listed detection and which need continuous thermal monitoring, talk to the AVIAN team. We can help you build a coverage plan your insurer can review.
Drew Hanover
CTO & Co-Founder
Get new AVIAN insights in your inbox
We'll send practical notes on industrial fire prevention, thermal monitoring, and customer learnings. No noise.
The dedicated section gives designers clear requirements for using thermal imaging inside the fire alarm system. Listing and approval routes include UL 2684 and FM 3260, supporting earlier detection of developing heat.
This guide explains what changed, what did not, and what it means from two points of view: the insurer pricing the risk and the manufacturer running the plant. We also explain where AVIAN fits.
1. A new definition (3.3.79.26). A thermal image fire detector is "an initiating device that senses overheated combustible material by imaging in the long-wave infrared wavelengths (i.e., far infrared) using a focal plane array." In plain English: a thermal camera that can start a fire alarm signal. The definition of "detector" itself was also broadened to include sensors that respond to light and sound, to make room for new detection methods.
2. A new section on design and installation (17.12). The technical committee explained why it was needed. Thermal imagers are technically radiant energy detectors, but the existing radiant energy rules were written for traditional non-imaging flame and spark detectors. New products look for overheated areas across a whole field of view, so they needed their own rules.
Section 17.12 is short. Most of its weight comes from a few requirements. The table below summarizes them based on the committee's first revision text and published summaries from Consulting-Specifying Engineer. Check the published edition for exact wording.
Requirement
What it means in practice
Listed for fire detection, including hardware and software
Specify a system listed for fire detection, covering its hardware, software, and intended application.
Performance-based design (Section 17.3)
There is no simple spacing table. An engineer designs coverage around the hazard and documents the objectives.
Clear line of sight to the protected hazard
The detector must see the thing that can burn. Obstructions, racking, and enclosures matter.
No pan-tilt mounts unless listed for movement
Detection is expected from a fixed view, not a camera that sweeps away from the hazard.
Outputs to other systems only through manufacturer-provided connections
Signals can feed PLCs or other systems, but only through outputs designed for that purpose.
Controls and software protected from unauthorized changes
Alarm settings cannot be casually edited. Configuration must be locked down.
Any software or setting change retested under Chapter 14
Changing a zone or threshold is a fire alarm change. It needs testing and records.
Supervisory signal if the lens is blocked or dirty
The system must tell you when it can no longer see. This matters in dusty plants.
Able to alarm on temperature rate of rise in the field of view
The detector must catch fast-developing heat, not only a fixed temperature threshold.
Two things stand out.
First, the code treats a thermal fire detector as a system, not just a camera. Software, settings, outputs, and supervision are all in scope.
Second, the code assumes the view can degrade. Dirt, dust, and blocked lenses are named failure modes. Anyone who has run a camera in a sawmill or recycling plant knows why.
UL 2684 and FM 3260: Listing and Approval Routes
Section 17.12.1 requires listing for fire detection. It does not name UL as the sole listing organization or require UL 2684 as the only route. UL 2684 listing and FM 3260 approval provide paths for thermal fire detection and fire alarm panel integration.
UL 2684, Video and Thermal Image Detectors for Fire Alarm Systems, covers imaging detectors used as part of fire alarm systems under NFPA 72. Its scope includes detecting heat at infrared wavelengths with a focal plane array, for indoor use and, for thermal detectors, outdoor use. Its current edition was ANSI approved in August 2025.
On September 22, 2026, Teledyne FLIR announced that its A40, A50, and A70 cameras were the first thermal imagers listed to UL 2684.
For either route, match the listed or approved configuration to the hazard, panel interface, and installation requirements. The fire alarm designer and AHJ confirm the application as part of the system design.
What Did Not Change
The new section fits into the facility's existing fire protection design:
Nothing requires you to install thermal cameras. The 2025 edition sets rules for thermal image fire detectors when they are used. It does not mandate them.
Your jurisdiction decides which edition applies. States and cities adopt NFPA 72 on their own schedule. Many sites still operate under older editions.
Sprinklers, smoke detection, and suppression stay. A thermal detector covers only what it can see. It does not replace code-required protection elsewhere.
Specify the listing for the application. UL 2684 listing and FM 3260 approval are routes to consider alongside the system design and panel interface.
The code keeps moving. The committee is working on the 2028 edition now. Expect refinements as field experience grows.
For Insurers
For underwriters, brokers, and risk engineers, the change gives thermal monitoring a vocabulary it did not have before.
Until now, a facility that said "we have thermal cameras" could mean almost anything. A handheld used once a quarter. A fixed camera that emails a supervisor. A fully engineered detection system tied to shutdowns. The underwriting file rarely made the difference clear.
NFPA 72, together with listing and approval routes such as UL 2684 and FM 3260, gives thermal systems clear roles in the protection plan.
Three roles thermal cameras can play
Listed fire detection. A thermal image fire detector, listed to UL 2684 or approved to FM 3260, designed under Section 17.12 and connected to the fire alarm system. It carries code standing, supervision, and a Chapter 14 testing record.
Supplemental early warning and condition monitoring. A fixed thermal monitoring system that watches equipment and material, alerts operations and maintenance, and often triggers PLC actions. Its focus is prevention: catching the hot bearing, loose connection, or smoldering load before it becomes a fire.
Both. Listed detection where code or policy requires it, plus supplemental monitoring on the assets most likely to start the fire.
Each role deserves credit for different reasons. Listed detection reduces the severity of a fire that has started by alarming earlier. Supplemental monitoring reduces frequency by stopping ignition sources. Many industrial losses begin as heat long before smoke. That prevention work gives the risk engineer measurable evidence of how the facility catches and resolves developing hazards.
What to ask during a risk review
Is the thermal system part of the fire alarm system, or a supplemental layer?
If listed, to which standard: UL 2684, FM 3260, or something else?
Who designed the coverage, and is there a written performance-based design?
Which hazards are in direct line of sight, and which are not?
How does the system report a blocked, dirty, or offline camera?
Who can change alarm settings, and is every change logged and tested?
Where do alarms go, and how fast does someone respond?
Can the site show real event history and corrective actions from the last 12 months?
Evidence of effective protection
A coverage map shows which surfaces and hazards the cameras can see. Event records show how quickly teams investigate alerts and close corrective actions. For a fire alarm application, the listing or approval documents and manufacturer's test records complete the picture.
Together, those records show how the system performs in daily operation and how the facility responds to developing heat.
If you run a sawmill, recycling plant, pellet mill, food plant, or any heavy industrial site, the first question is simple: does this force me to do anything?
Usually not. The code does not require thermal detection. But it changes three conversations you are likely to have soon.
1. Your insurer and AHJ now have a reference point
Expect more specific questions at renewal and during plan review. "What role does your thermal system play?" is now a fair question with a defined answer. Have one ready.
2. You need to decide what job the camera is doing
Before buying anything, decide which of these you need:
Code-required or insurer-required fire detection for a specific hazard. That points to a listed thermal image fire detector, a fire protection engineer, and your fire alarm contractor.
Fire prevention and uptime on conveyors, motors, bearings, panels, dust systems, and material piles. That points to a thermal monitoring system that learns normal behavior, alerts your team, and integrates with your controls.
Both, which is common in high-risk plants.
These functions can work together. Fire alarm initiation provides a defined emergency response, while continuous temperature trends help maintenance find and correct the underlying equipment problem. Choose the system and integration around both objectives.
3. Plan for reliable operation
If you install listed thermal image fire detectors, plan for what Section 17.12 implies:
Engineering. Performance-based design means someone has to document objectives, hazards, and coverage.
Fixed, clean views. Plan mounts, guards, and lens cleaning. In dusty areas, the supervisory signal for a dirty lens will tell you how often.
Change control. Adjusting a zone is now a fire alarm change. Budget time for retesting and records.
Ownership. Your fire alarm contractor, controls team, and maintenance team all touch this system. Decide who owns what.
Clear responsibilities and a practical maintenance schedule keep detection reliable.
Where thermal prevention still pays off
Most plant fires do not start in open space. They start at equipment: a dragging roller, an overloaded motor, a hot electrical connection, a dust duct carrying embers. The same heat that signals fire risk also signals a coming failure.
That is why many manufacturers get more value from continuous thermal monitoring on critical assets than from detection alone. It prevents fires and downtime from the same data. See what condition-based monitoring with thermal imaging looks like in practice.
What This Means for AVIAN Customers
We have been saying for years that heat is the first warning. NFPA 72 now agrees that heat seen through a thermal imager is a legitimate fire signal. That is good for the whole category.
AVIAN turns developing heat into action. The AVIAN T100 continuously monitors equipment and material, learns normal temperature behavior, and gives teams the thermal and visible context to respond early. Operations can investigate a hot load, maintenance can correct a failing bearing, and plant controls can act on an alarm before the problem escalates.
The engineering principles in 17.12 are already how we deploy. The code's requirements describe what a reliable thermal system needs. AVIAN was built around the same ideas for prevention.
NFPA 72 17.12 principle
How AVIAN approaches it
Clear line of sight to the hazard
Coverage is planned asset by asset, with fixed T100 mounts aimed at the conveyors, motors, panels, and piles that matter.
Know when the view is lost
Tamper detection alerts when a camera is blocked, misaligned, or offline.
Catch developing heat, not just a fixed limit
The T100 learns each asset's normal temperature and flags drift as it starts, filtered by visual context to cut nuisance alarms.
Access is controlled under our SOC 2 Type II program, and every alert, acknowledgement, and response time is logged.
An AVIAN deployment brings coverage planning, camera-status monitoring, controlled settings, and response records into the same workflow. That gives plant teams useful operating evidence and insurers a clearer picture of how developing hazards are handled.
Connect detection with a practical response. Build the protection plan around:
Fire detection and alarm integration matched to the hazard and applicable listing or approval.
AVIAN on the equipment and material most likely to start a fire, where abnormal heat appears hours or days before an alarm-worthy event.
One response workflow that routes heat alerts to the people and PLCs that can act.
For insurers, that plan is easy to document. For plant teams, it means one system pays for itself through avoided downtime while also lowering fire risk.
The Bottom Line
NFPA 72 2025 did not make thermal cameras mandatory. It made them legitimate fire alarm devices, with rules to match: listing, engineered design, line of sight, supervision, locked configuration, and documented testing.
For insurers, the useful question is now specific: what role does this thermal system play, and what evidence backs it?
For manufacturers, the useful question is: what job do we need the camera to do? Code detection, prevention and uptime, or both?
Answer those two questions honestly and the rest of the decision gets easier.
If you want help mapping which areas of your facility need listed detection and which need continuous thermal monitoring, talk to the AVIAN team. We can help you build a coverage plan your insurer can review.
Drew Hanover
CTO & Co-Founder
Get new AVIAN insights in your inbox
We'll send practical notes on industrial fire prevention, thermal monitoring, and customer learnings. No noise.